User Manual

Day-to-day operation, settings and troubleshooting. Start here if the product is already set up.

Questions answered in Shanghai Shiny Electronic manuals

How do I perform a self‑test on the SH100 detector?

Press the red control button for less than 0.6 seconds; the indicator lights flash red, yellow, green and the buzzer sounds for three seconds.

From: Shanghai Shiny Electronic SH100 Standalone Combustible Gas Detector User Manual

What should I do if the detector continuously sounds an alarm?

Check whether the sensitivity is set too high or there is a circuit fault; recalibrate the unit or return it to the manufacturer for repair.

From: Shanghai Shiny Electronic SH100 Standalone Combustible Gas Detector User Manual

What is the alarm concentration for methane?

The detector alarms when methane reaches 15% of the lower explosive limit (LEL).

From: Shanghai Shiny Electronic SH0105 B Combustible Gas Detector User Manual

How quickly does the detector respond to a gas leak?

The response time is less than or equal to 30 seconds.

From: Shanghai Shiny Electronic SH0105 B Combustible Gas Detector User Manual